| "S"-SERIES SIMPLEX CONTROLS |
NEMA 1 - INDOOR
 |
NEMA 4X - OUTDOOR
 |
SIMPLEX SEQUENCE OF OPERATION
The wastewater is discharged into a pump tank. This tank is provided with a pump controlled by three (3) float switches to control, by volume, each dose to be discharged. When water rises in the chamber, the lower float will rise. Water will continue to rise until the middle float rises and actuates the pump. The pumping volume may be adjusted by increasing the separation between the lower and middle float.
In the event of mechanical failure, the water will continue to rise above the middle float. Upon the alarm float rising, the alarm contact will be closed. The alarm light and the audible alarm shall activate. The controller shall continue to sound the alarm until the system is serviced. The alarm test-off-normal (test-normal-silence for auto-reset alarm)switch may be turned to the off (silence) position to silence the audible portion of the alarm and turn off the top mounted light.
For the pump to be automatically actuated, the pump switch must be on "auto". The pump may also be operated in the "manual" position.
"S" Series Simplex Dose On Demand Controls (Single Phase and Three Phase)
Basic Control Designation Terms: (All features and Options must be designated in model number if desired.) |
| ___S___ | ______ | ______ | ___4___ | - | ______ |
Control Series |
Alarm Feature (if desired) |
Breaker Feature (if desired) |
Enclosure NEMA 1 Indoor NEMA 4x Outdoor |
| Options (If desired) |
Typical Model Number - SAB124-FJL.
(Simplex control with alarm, breakers-1ph/230v, Nema 4x enclosure, flasher, upgraded contactor, and locking hasp.) |
 |
Basic "S" Pump Control Includes:
- Nema rated enclosure w/hinged door (Nema 1 steel or Nema 4x fiberglass)
- Removable aluminum backplate for component mounting.
- Duty rated pump contactor 16A @ 115/230V/460V
- Hand-Off-Auto Toggle Switch
- Power and pump run indicator light
- 2A control fuse
- Finger-safe terminal blocks
- Neatly bundled wiring harness
- 115V control transformer w/ fused secondary
(Three-phase units only)
- U.L. APPROVED AND LABELED
Alarm "A" Feature (If desired) Includes:
- 85db @ 10 ft. alarm horn
- Test-Off-Normal toggle switch
- High level indicator light, 40 Watt red lexan alarm light (Outdoor units only)
- Dry remote alarm contacts (Outdoor and all three-phase units only)
- 120V Powered remote alarm contacts (Three-phase units only)
|
| Breaker "B" Feature (If desired) Includes: |
|   | For units without alarm: | -Molded case pump/control circuit breaker |
| For units with alarm: | -Molded case pump circuit breaker |
| | -Molded case alarm/control breaker |
| For 460v/3-phase units: | -Motor protector for pump (combination short circuit/overload) |
| | -Molded case alarm/control breaker |
| ITEM | DESCRIPTION |
| ARSAB-B1959P | ARSAB124-AFJ2KLS, AUTO REVERSING SIMPLEX, 115V/230V, 1 PH |
| SA1-B1250P | SA1-AJ SIMPLEX W/ ALARM |
| SA4-B1528P | SA4-AFJL SIMPLEX W/ ALARM & FLASH |
| SAB-B1101P | SAB121-J SIMPLEX W/ ALARM & BREAKER |
| SAB-B1559P | SAB124-AFJL SIMPLEX W/ ALARM & BREAKER |
| SAB-B1569P | SAB124-AEFJL SIMPLEX W/ ALARM & ETM |
| SAB-B1686P | SAB124-ACEFJL SIMPLEX W/ ALARM, COUNTER & ETM |
| SAP-B1704P | SAP324-AJ1L, SIMPLEX, 230V, 3 PHASE |
| SAP-B1728P | SAP341-J1, SIMPLEX, 460V, 3 PHASE |
| SAP-B1737P | SAP344-AJ1L, SIMPLEX, 460V, 3 PHASE |
| SAP-B1796P | SAP321-J1, SIMPLEX, 230V, 3 PHASE |
| SAP-B1859P | SAP384-AJ1L, SIMPLEX, 208V, 3 PHASE |
|
|